Stacking Shipping Containers on Land for an Off-Axis Detector - Load-Bearing Capacity and Safety





Stacking Shipping Containers on Land for an Off-Axis Detector
J. Cooper, J. Kilmer, B. Wands
Fermi National Accelerator Laboratory, Batavia, IL 60510

May 29, 2003




Introduction
Corner Post Geometry and Compressive Load-Bearing Capacity
Corner Fittings
Safety Factor for Stacking Containers on Land

Introduction

Fig. 1 shows a typical International Standards Organization (ISO) Series 1 shipping container.


Figure 1. ISO Series 1 Shipping Container

These containers are designed to make vertical contact with each other through discrete corner fittings; when stacked, all vertical force is transferred through these fittings, in turn loading the corner posts, and not the walls, of the container. The number of containers which can be stacked on each other is determined by the strength of the corner posts.

ISO Standard 1496(1) states that the corner posts of ISO Series 1 containers should be tested to a load of 86,400 kg (190,480 lbs). This is the load applied to the posts of the bottom container in an 8-on-1 stack of 24,000 kg (gross weight) containers, multiplied by a factor of 1.8. This extra factor is used to take into account “conditions aboard ship and the relative eccentricities between superimposed containers.”(1) The “conditions aboard ship” were derived from a 1964 study of maximum acceleration values under the worst sea and wind conditions.(2)

Calculating the safe stacking height for loaded containers on land requires some understanding of the corner posts, their material properties, possible failure modes, and what constitutes an adequate factor of safety.


Corner Post Geometry and Compressive Load-Bearing Capacity


Corner post steels typically correspond to the specification ASTM A-572, with a yield stress of 47,000 psi, and an ultimate stress of 70,000 psi. This is a low alloy columbium or vanadium steel commonly used for high-strength steel weldments, such as bridges. The load-bearing characteristics of corners posts are complex, because in a walled container the posts receive substantial lateral stability, and compressive cross
sectional area, from the participation of the walls and doors.

The corner post can fail in two ways: The first is collapse, or buckling. This occurs in a slender column when the compressive load reaches a critical load Pcr which is so large that the column can no longer recover from small lateral displacements along its length. The result is sudden and catastrophic loss of stiffness, and gross deformation of the column and its attached material.

A second type of failure can occur if the compressive load Pcomp exceeds the value SyA, where Sy is the yield stress of the material, and A is the cross sectional area of the post. Even a column which is stable against buckling failure can fail from compressive yielding. Failures of this type are rare for columns, since the yielding will tend to produce larger cross sectional area through plastic deformation, and eventually become
self-limiting. This self-limit may not be reached before even a very short column becomes unstable, however, resulting in a type of collapse that is characterized by large amounts of plastic deformation.

The most likely failure mode, given the substantial lateral constraint offered by the walls, is probably a combination of collapse and gross yielding, a type of failure referred to as elastic/plastic collapse.

The calculation of collapse (buckling) loads for long, slender steel columns uses the Euler equation:

Pcr = kπ2EI/L2

where Pcr = critical (collapse) load
          E = modulus of elasticity of steel = 30e6 psi
          I = minimum moment of inertia of section
          L = length of column
          k = factor for end rotational restraint (theoretical range from 1-4)

For the corner posts, the degree of end rotational restraint is difficult to quantify. The top, bottom, and side rails will serve to provide substantial restraint, and even the corner fitting contact of the loading container above a corner post will tend to limit rotation. Therefore, a k factor of 2 is chosen for calculating the estimates of collapse load.(3) This is less than the complete rotational restraint (k = 4), but greater than free rotation (k = 1).

In addition to resisting collapse, the corner post must also work at a compressive stress that is below the yield of the material. Corner posts will yield at a stress of 47,000 psi. Therefore, the minimum cross sectional area for resisting the corner post loads is A = 190,840/47,000 = 4.05 in2
.
While the minimum performance of a corner post is standardized via ISO, the actual geometry of the post is not. Manufacturers have explored many different designs for many different types of containers, all of which will pass the ISO test load of 86,400 kg or 190,840 pounds. Figure 2 shows the most common corner post cross-sections at the door and walled ends of a Series 1 container. These posts are made of 6mm thick pressed steel shapes welded together along the length of the post. In the case of the door end post, a piece of hot rolled channel 113 x 40 x 10 mm is welded to the 6mm plate. Both posts in Figure 2 have adequate cross sectional area from the standpoint of compressive stress. However, the Door End post (a), has a collapse load which is less than the load required by the ISO standard, and therefore must rely on interaction with the walls and doors of the container to produce the necessary load-bearing capacity.

       area = 5.7 in2
       Imin = 2.7 in4
       Pcr = 175,000 lbs
       Pcomp = 267,900 lbs
       area = 5.7 in2
       Imin = 11.3 in4
       Pcr = 725,000 lbs
       Pcomp = 267,900 lbs

(a) Corner Post at Door End(b) Corner Post at Walled End

Figure 2. Corner Post Cross Sections - Properties and Load Capacities without Wall/Door Participation

The effect of participation of the walls and doors is illustrated in Fig. 3 The profile of Fig. 2(a) has been used with a 3-inch wide strip of adjacent container sidewall (3.6 mm thick) and a 2-inch wide strip of door panel (2 mm thick), to form a column of considerably higher strength than the profile of Fig. 2(a) alone. The cross section shown, with walls, has a critical load of approximately 252,000 lbs, which is well above the 175,000 lbs of the corner post alone, and well above the 190,480 lbs required by the ISO Standard.

These calculations show that the door is an important part of the load path under stacking, providing additional cross-sectional area for compression and stability. The door also acts as a sheer wall, preventing the parallelogram deformation of the end referred to as “racking” or “sidesway.” For these reasons, in commercial practice, the doors on a container within a stack are presumably never opened. This is not a constraint on the way the containers are used in commerce, since only one container at a time is loaded or unloaded at terminals, with stacking occurring only during transit.

        area = 6.3 in2
        Imin = 3.92 in4
        Pcr = 252,000 lbs
         Pcr = 252,000 lbs


Figure 3. Corner Post from Fig. 2(a) showing increase in buckling strength due to participation of wall


Corner Fittings


The corner fittings shown in Figure 1 are an integral part of the load-bearing column in the container. ISO 1161-1984(E)(4) states “Corner fittings for Series 1 freight containers shall be capable of withstanding the loads calculated in accordance with the requirements of ISO 1496/1 for Series 1 containers.” This means that the bottom corner fitting of the bottom container in a stack must withstand the weight of the containers
stacked above it, plus the weight of the bottom container itself. The maximum load which a single corner fitting must take is then

Ptot = 190,480 + (52,800/4) = 203,680 lbs 

A typical corner fitting is shown in Fig. 4.. The cross sectional area of this fitting is shown in Fig. 5. The total cross sectional area available for compression is 10.15 in2. This results in an average compressive stress under maximum load of 20,067 psi.

Corner fittings are typically cast and machined from A-216 steel, which has a minimum specified yield stress of 40,000 psi. Therefore, under maximum load, a corner fitting of the cross section shown below operates with a safety factor on yield of nearly 2.0

                            area = 10.15 in2


         Figure 4. Corner Fitting          Figure 5. Fitting Cross Section


Safety Factor for Stacking Containers on Land


A safety factor for the corner posts in the bottom container of a stack can be defined as

SF = Fcp-fail/Fcp-act

where SF = safety factor
          Fcp-act = actual operating load on corner post
          Fcp-fail = failure load of corner post


The ISO Standard, however, does not define a force Fcp-fail; rather, it specifies the load that each corner post must withstand without failure. In this sense, the specified load is a proof load, Fcp_proof, which is simply a load which each corner post must be shown capable of resisting. For the purposes of calculating a safety factor, the specified test load can be thought of as an absolute lower limit on the failure load. Any safety factor calculated with Fcp-fail = Fcp-proof will be smaller than the actual safety factor, since Fcp-proof is always smaller than Fcp-fail .

Using the expression above, the safety factor of an 8-on-1 stack of containers on land is at least 1.8 . Safety factors in engineering commonly range from 1.25 to 2.0 or greater, depending on the amount of confidence the designer has in material performance and load characterization. The AISC Steel Construction Code(5), for example, uses a safety factor of 2 for column loading; however, conservative design in civil structures is necessary because there is typically no load-testing of the parts; they are designed, manufactured, and set in place with only the calculation and fabrication standards serving as proof of merit. Aircraft design, however, uses safety factors closer to 1.25, due to the great penalties incurred by excess weight. The extremely rigorous materials and testing programs common in the aviation industry justify these smaller safety factors.

Because the corner posts of all containers are known to have been tested to the load stipulated by ISO 1496 with no failures occurring at a load that is less than the test load, a safety factor of about 1.5 is adequate for a stack of containers on land. Table I shows the safety factor on the corner post loading of the bottom container in a stack, for stacks of various heights. This table is based on the application of the equation for safety factor, with Fcp-fail = Fcp-proof = 190,480 lbs, and containers of 52,910 lbs gross weight:

Table I. Safety Factors on Land for Various Stack Heights on Land with Container Corner Post Capacity of 190,480 lbs (86,400 kg)

Number of Containers Stacked on One
Total Height of Stack
Safety Factor on Corner Post Loading
8
9
1.80
9
10
1.60
10
11
1.44
11
12
1.31

The table shows that we can stack 9-on-1 on land, and maintain a safety factor of greater than 1.5.

Possible Modifications


For a final detector design, good engineering practice would require that the corner posts of several containers be loaded to failure to more precisely determine Fcp_fail, from which more accurate stacking safety factors could be calculated. Some advantage might be taken of the fact that while Fcp-fail is not known, it is certainly higher than 190,480 lbs (86,400 kg). If the measured failure load is just 4% higher than the test (proof) load, the safety factor on a 10-on-1 stack becomes 1.5, and stacking to that height
becomes defensible.

Some vendors advertise containers with a higher capacity(6) than the ISO Series 1 standard, and advantage could be taken of the greater payload, as well as the higher post strength, in configuring the detector array. The typical higher post rating quoted is 214,290 lbs (97,400 kg), allowing exactly 9 on 1 stacking of 52,910 lb (24,000 kg) containers at sea and therefore allowing 10 on 1 on land with a safety factor of (9/8)*(1.44) = 1.62.

Similarly, if the Off-Axis detector density is small enough that our standard gross weight container is less than 52,910 lbs (24,000 kg), then even higher stacks could be supported. Table II shows the stack heights possible when the higher strength containers are used. A container volume of 33.2 m3 is assumed with a tare weight of 2,250 kg and four different detector gross weights of 22,150 kg, 24,000 kg, 26,000 kg and 0,480 kg. The 30,480 kg number is the vendor quoted maximum gross weight for the higher strength containers. Comparing Tables I and II shows that the higher strength posts lead to the same height stacks as the lower strength posts for containers of density 0.75 gm/cc vs. 0.66 gm/cc.

Table II. Stack Heights on Land for Various Detector Densities with Container Corner Post Capacity of 214,290 lbs (97,400 kg)

Number of
Containers
Stacked on
One
Total
Height
of Stack
(m)
Safety Factor on Corner Post Loading
with payload
density =
0.60 g/cc
(22,150 kg gross)
with payload
density =
0.66 g/cc
(24,000 kg gross)
with payload
density =
0.75 g/cc
(27,150 kg gross)
with payload
density =
0.85 g/cc
(30,480 kg gross)
8 on 1
23.3
2.20
2.03
1.80
1.60
9 on 1
25.9
1.95
1.80
1.59
1.42
10 on 1
28.5
1.76
1.62
1.43
1.28
11 on 1
31.1
1.60
1.48
1.30
1.16

Conclusion


Stacking ISO containers 10 high on land is reasonable, and stacks as high as 12 may be possible depending on the type of container purchased and on the loading of the container with Off-Axis detector elements. For a final detector design, good engineering practice would require that the corner posts of the selected containers be loaded to failure to more accurately determine the safety factor of the stacked array.

References


1. ISO 1496-1:1990 Series 1 freight containers – Specification and testing – Part 1: General cargo containers for general purposes

2. ISO/TR 15070:1996(E) Series 1 freight containers – Rationale for structural test criteria

3. “Commentary on the Specification for the Design, Fabrication and Erection of Structural Steel for Buildings”, Section 1.8, American Institute of Steel Construction, 1978

4. ISO 1161-1984(E) Series 1 freight containers – Corner fittings – Specification

5. “Commentary on the Specification for the Design, Fabrication and Erection of Structural Steel for Buildings”, Section 1.5.1.3, American Institute of Steel Construction, 1978

6. We have several specification documents from container vendors that stipulate a higher load capacity, but no details on just how this is accomplished by any container manufacturer via changes in the post configuration. We suspect that these vendors may just be taking advantage of a specification requiring a higher measured failure load as discussed in the preceding paragraph. After all, our post calculations for Figures 2(b) and Figure 3 indicate that these “standard” posts should easily pass a failure load test at 214,290 lbs vs. the original ISO test at 190,480 lbs.


More articles in Shipping Container Homes & Buildings:

Overview of Modular Design Strategy of the Shipping Container Architecture in Cold Regions

Educational Adaptation of Cargo Container Design Features

Using Container Structures in Architecture and Urban Design

Feasibility of ISO shipping container as transitional shelter - a review

The Study of Fire Safety for Multi-Storey Shipping Container Hotel - A Case Study in Muar PPT Hotel

Innovations in shaping the residential and retail buildings. Functional and pro-environmental potential of shipping containers in architecture

Exploration and Analysis of Shipping Container Architectural Adaptability Design in Central Jiangxi Province




Stacking Shipping Containers on Land for an Off-Axis Detector - Load-Bearing Capacity and Safety